KNX Smart Lighting Switch Actuator
Application Scenarios:Office buildings,shopping malls,libraries, convention and exhibition centers and other occasions that require intelligent control of lighting
PRODUCT OVERVIEW
The actuator series products are modular installation equipment,according to the number of circuits,there are 4 channels,8 channels,12 channels of output,according To different functions,there are two kinds of current detection and ordinary two.The terminal of the device connected to the system uses an EIB but terminal block.The Actuator does not require additional supply voltage and is directly connected to the AC power supply.The assignment of physical addresses as well as the setting of parameters can be done using the engineering tool software ETS(version ETS 5.6.5 or later).Switching actuators can switch from 4 to 12 independent electrical AC Loads,with a maximum load current of 16A output from each on/off actuator,all of which can be manually turned on or off.The switching status is visible.
KNX SYSTEM TOPOLOGICAL DIAGRAM
KEY FEATURE
Basic Parameter |
||||
Item |
Data |
Notes |
||
KNX interface |
Baud rate:9600 |
EIB terminal wiring |
||
Interference Index |
||||
Electrostatic discharge |
|
Ⅲ |
|
|
Radio frequency electromagnetic field radiated |
|
Ⅲ |
Ⅲ |
|
Electrical fast Transient pulse |
|
Ⅲ |
|
|
Surge |
|
Ⅲl |
Ⅲ |
I |
Radio frequency conduction |
|
Ⅲ |
|
|
Working Environment |
||||
Working voltage |
21-30V |
Bus Supply |
||
EIB/KNX current Power consumption |
<12mA |
|||
EIB/KNX Power Consumption |
Max.360mW |
|||
Output Normal Value |
Model |
HKL/K0416412C HKL/K0416412J |
HKL/K0816412C HKL/K0816412J |
HKL/K1216412C HKL/K1216412J |
Channel |
4 |
8 |
12 |
|
Un(rated Voltage) |
250VAC(50-60HZ) |
250VAC(50-60HZ) |
250VAC(50-60H Z) |
|
In (rate current) |
16A |
16A |
16A |
|
Max Switching Current |
20A/250VAC |
20A/250VAC |
20A/250VAC |
|
Max load loss |
2w |
6w |
8w |
|
Current detecting range * |
50mA-16A |
50mA-16A |
50mA-16A |
Min detecting load * |
10w |
10w |
10w |
|
Current detecting Accuracy * |
±5% |
±5% |
±5% |
|
Output life |
Mechanical life |
>1000000 times |
||
Electrical life |
>10000 times |
|||
Out on/off time |
Single channel Relay operation cycle |
50ms |
||
Starting on/off delay time |
20ms |
|||
connection |
EIB/KNX |
EIB terminal(diameter 0.8mm) |
||
Load wiring terminal |
Screw wiring terminal |
|||
Operation & instructions |
Red LED & button |
Physical address assignment |
||
Green LED flicker |
Show application layer normally working |
|||
Green LED constant lighting Or extinguish |
Downloading data or working abnormal |
|||
Touch point position |
Close - channel open |
|||
Break off-channel close |
||||
Shell protection |
IP20 |
|||
Safety grade |
Ⅱ |
|||
Environment temperature |
working |
-5℃~+45℃ |
||
storage |
-25℃~+70℃ |
|||
transportation |
-25℃~+70℃ |
|||
humidity |
5-95%,no condensation |
|
||
appearance |
ABS shell |
Flame retardant UL94V-0 |
||
installation |
DIN rail module parts |
35mm din rail |
||
Dimension |
HKL/K0416412C HKL/K0416412J |
72*90*64MM |
|
|
HKL/K0816412C HKL/K0816412] |
145*90*64MM |
|
||
HKL/K1216412C HKL/K1216412J |
216*90*64MM |
|
||
Weight |
HKL/K0416412C HKL/K0416412J |
260g 220g |
|
|
HKL/K0816412C HKL/K0816412J |
460g 420g |
|
Lamp load expected |
|
|
Electrical life |
100000 cycle |
30000 cycle |
Incandescent light lamp |
1250W |
2500 W |
No compensation type fluorescent lamp |
1250W |
2500 W |
Parallel compensation type Fluorescent lamp |
650W/70μF |
1300W/140μF |
Double tube fluorescent lamp |
2x1200W |
2x2500W |
230VAC iodine-tungsten lamp/halogen lamp |
1200W |
2500 W |
Low voltage halogen lamp with inductor transformer |
1000W |
2000W |
Low voltage halogen lamp with electric transformer |
500VA |
500VA |
No compensation type mercury / sodium lamp |
1000W |
2000W |
Parallel compensation type mercury / sodium lamp |
1000W/70μF |
2000W/140μF |
No compensation type alkyd resin lamp |
800W |
1600W |
Parallel compensation alkyd resin lamp |
560W/70μF |
1100 W/140μF |
4 ways: HKL/K0416412C HKL/K0416412J
8 ways: HKL/K0816412C HKL/K0816412J
12ways: HKL/K1216412C HKL/K1216412J
Appearance & Dimension
4 channels actuator dimension 8 channels actuator dimension
12 channels actuator dimension
Interface introduction( base on 4 channels actuator
Installation
4 channels din rail installaton
8 channels din rail installaton
12 channels din rail installaton
wiring
4 channels actuator wiring
8 channels actuator wiring
12 channels actuator wiring
KNX Smart Lighting Switch Actuator