LPC96P Low Voltage Integrated Monitoring Device
Application Scenarios:Medium /High Voltage Cabinet,Low Voltage Wiring Cabinet
PRODUCT OVERVIEW
The device in line with the distribution network standardized design 0.4kv Los-voltage switchgear design specification requirements,large screen dot matrix display,using 96,shape and very short gauge depth,especially suitable for applications with narrow installation space,industrial standard wide temperature LCD display,with good high and low temperature display characteristics,the terminal can achieve full power measurement and display,including dynamic alarm,switching input and output status,SOE event recording,compound rate,loop load ratio display,harmonics,etc,support dual communication,transmission output function.It has the function of fault judgment such as short circuit,overload,phase loss,phase sequence,and zero break.It adopts snap-on fixed design to improve the efficiency of cabinet assembly,which is suitable for power industry switchgear distribution panel circuit distribution measurement and control.
KEY FEATURES
Signal Input |
Line |
Three phase 3 line, 3 phase, 4 line |
|
Frequency |
45~65Hz |
||
Voltage |
AC 57.7/100V, 230/380V |
||
Over load:1.2 times the rated value(continuous); 1.4 times rated voltage(10s), 2, times the rated value 1s |
|||
Power consumption:< 0.5VA (each line) |
|||
Current |
AC 1A, 5A |
||
Overload: 1.2 times the rated value (continuous); 20 times the rated value /10 second. |
|||
Consumption: < 0.25VA (each line) |
|||
Accuracy |
V、C、P |
0.2 |
|
Active |
0.5s |
||
Reactive |
2 |
||
Zero Current (residue) |
20mA~1A(±1%); 1A~2A(±2.5%) |
||
Harmonic Sampling |
128point/cycle, FFT method,breakdown judging |
||
Power Supply |
Range: AC/DC 85V~265V Consumption: main power consumption≤5VA. |
||
Relay Output |
Touch point type: normally open (level output jog mode) Touch point capacity: AC 250V/3A DC 30V/3A. |
||
Power Pulse Output |
Output mode: optocoupler pulse of open collector |
||
Switch Alue Output |
Support dry contact input, DC12V power supply built-in; Resolution≤5mS |
||
Communication |
RS485 interface Modbus-RTU protocol or LT645 stipulation; |
||
Lora, zigbee (wireless communication optional) |
|||
Security |
Working Pressure |
Among APS, voltage signal, current signal AC 2kV/1min; Working frequency among switch value, pulse output, communication, AC 1kV/1min. |
|
Insulation resistance |
Input, output terminal to the chassis>100MΩ. |
||
Electromagnetic Compatibility |
Reach IEC 61000 standard (level 4) |
||
Level of Protection |
IP51 (front), IP30 (inside)(except for terminal) |
||
Working Life Designed |
10years |
||
Working Environment
|
Meter Working Temperature: -25℃~+80℃; LCD Working Temperature: -20℃~+80℃; Storage Temperature: -40℃~+85℃; Relative Humidity: ≤99% no condensation; Elevation: ≤2500m. |
LPC96P Low Voltage Integrated Monitoring Device